January 2023 |
SCADA Data - Monthly Averages
Water Treatment Plant |
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
37.41
|
Brantford POE
|
Flow Rate
|
ML/d
|
31.00
|
Grand River
|
Turbidity
|
NTU
|
7.65
|
Filter 1
|
Turbidity
|
NTU
|
0.031
|
Filter 2
|
Turbidity
|
NTU
|
0.027
|
Filter 3
|
Turbidity
|
NTU
|
0.033
|
Filter 4
|
Turbidity
|
NTU
|
0.038
|
Filter 5
|
Turbidity
|
NTU
|
0.031
|
Filter 6
|
Turbidity
|
NTU
|
0.044
|
Filter 7
|
Turbidity
|
NTU
|
0.041
|
Filter 8
|
Turbidity
|
NTU
|
0.039
|
Brantford POE
|
Turbidity
|
NTU
|
0.040
|
CCC Effluent
|
Log Removal
|
Not applicable
|
9.21
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.54
|
Brantford POE
|
Pressure
|
psi
|
97.01
|
SCADA Data - Monthly Averages
Distribution System |
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.46
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.45
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.64
|
Albion St. Booster
|
Pressure
|
psi
|
90.79
|
Tollgate Reservoir
|
Pressure
|
psi
|
57.24
|
Park Rd. Reservoir
|
Pressure
|
psi
|
78.86
|
Northwest Reservoir
|
Pressure
|
psi
|
85.37
|
Bell Lane
|
Pressure
|
psi
|
50.62
|
Fifth Ave
|
Pressure
|
psi
|
96.28
|
Lawren Harris
|
Pressure
|
psi
|
64.62
|
St. Andrews
|
Pressure
|
psi
|
93.75
|
Empey St.
|
Pressure
|
psi
|
82.70
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
Treatment Operators Analysis
Source | Parameter | Units | MAC | AO/OG | Minimum | Maximum | Average |
Grand River
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.05
|
0.32
|
0.13
|
Brantford POE
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.19
|
0.51
|
0.33
|
Grand River
|
True Colour
|
PtCo
|
Not applicable
|
Not applicable
|
12
|
27
|
19
|
Brantford POE
|
True Colour
|
PtCo
|
Not applicable
|
5
|
0.0
|
3
|
1
|
Brantford POE
|
Aluminum
|
mg/L
|
Not applicable
|
0.100
|
0.017
|
0.045
|
0.032
|
Grand River
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.097
|
0.188
|
0.149
|
Brantford POE
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.040
|
0.064
|
0.056
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
Not applicable
|
0.55
|
0.76
|
0.65
|
Brantford POE
|
Free chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
Not applicable
|
2.30
|
2.80
|
2.57
|
Brantford POE
|
Total Chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
2.50
|
2.90
|
2.67
|
Definitions:
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
February 2023 |
SCADA Data - Monthly Averages
Water Treatment Plant |
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
37.56
|
Brantford POE
|
Flow Rate
|
ML/d
|
30.72
|
Grand River
|
Turbidity
|
NTU
|
8.93
|
Filter 1
|
Turbidity
|
NTU
|
0.030
|
Filter 2
|
Turbidity
|
NTU
|
0.032
|
Filter 3
|
Turbidity
|
NTU
|
0.035
|
Filter 4
|
Turbidity
|
NTU
|
0.038
|
Filter 5
|
Turbidity
|
NTU
|
0.029
|
Filter 6
|
Turbidity
|
NTU
|
0.036
|
Filter 7
|
Turbidity
|
NTU
|
0.035
|
Filter 8
|
Turbidity
|
NTU
|
0.040
|
Brantford POE
|
Turbidity
|
NTU
|
0.041
|
CCC Effluent
|
Log Removal
|
Not applicable
|
8.59
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.51
|
Brantford POE
|
Pressure
|
psi
|
96.92
|
SCADA Data - Monthly Averages
Distribution System |
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.47
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.38
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.55
|
Albion St. Booster
|
Pressure
|
psi
|
90.90
|
Tollgate Reservoir
|
Pressure
|
psi
|
58.85
|
Park Rd. Reservoir
|
Pressure
|
psi
|
78.79
|
Northwest Reservoir
|
Pressure
|
psi
|
85.47
|
Bell Lane
|
Pressure
|
psi
|
50.57
|
Fifth Ave
|
Pressure
|
psi
|
96.23
|
Lawren Harris
|
Pressure
|
psi
|
64.88
|
St. Andrews
|
Pressure
|
psi
|
93.81
|
Empey St.
|
Pressure
|
psi
|
82.64
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
Treatment Operators Analysis
Source | Parameter | Units | MAC | AO/OG | Minimum | Maximum | Average |
Grand River
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.03
|
0.28
|
0.09
|
Brantford POE
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.17
|
0.43
|
0.31
|
Grand River
|
True Colour
|
PtCo
|
Not applicable
|
Not applicable
|
9
|
25
|
17
|
Brantford POE
|
True Colour
|
PtCo
|
Not applicable
|
5
|
0.0
|
4
|
1
|
Brantford POE
|
Aluminum
|
mg/L
|
Not applicable
|
0.100
|
0.018
|
0.048
|
0.031
|
Grand River
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.113
|
0.178
|
0.146
|
Brantford POE
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.037
|
0.066
|
0.054
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
Not applicable
|
0.55
|
0.80
|
0.67
|
Brantford POE
|
Free chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
Not applicable
|
2.40
|
2.80
|
2.51
|
Brantford POE
|
Total Chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
2.50
|
2.90
|
2.61
|
Definitions:
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
March 2023 |
SCADA Data - Monthly Averages
Water Treatment Plant |
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
36.95
|
Brantford POE
|
Flow Rate
|
ML/d
|
30.27
|
Grand River
|
Turbidity
|
NTU
|
8.91
|
Filter 1
|
Turbidity
|
NTU
|
0.030
|
Filter 2
|
Turbidity
|
NTU
|
0.033
|
Filter 3
|
Turbidity
|
NTU
|
0.036
|
Filter 4
|
Turbidity
|
NTU
|
0.039
|
Filter 5
|
Turbidity
|
NTU
|
0.029
|
Filter 6
|
Turbidity
|
NTU
|
0.036
|
Filter 7
|
Turbidity
|
NTU
|
0.036
|
Filter 8
|
Turbidity
|
NTU
|
0.040
|
Brantford POE
|
Turbidity
|
NTU
|
0.043
|
CCC Effluent
|
Log Removal
|
Not applicable
|
9.40
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.49
|
Brantford POE
|
Pressure
|
psi
|
97.06
|
SCADA Data - Monthly Averages
Distribution System |
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.35
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.29
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.51
|
Albion St. Booster
|
Pressure
|
psi
|
90.77
|
Tollgate Reservoir
|
Pressure
|
psi
|
58.43
|
Park Rd. Reservoir
|
Pressure
|
psi
|
78.81
|
Northwest Reservoir
|
Pressure
|
psi
|
85.78
|
Bell Lane
|
Pressure
|
psi
|
50.69
|
Fifth Ave
|
Pressure
|
psi
|
96.30
|
Lawren Harris
|
Pressure
|
psi
|
64.63
|
St. Andrews
|
Pressure
|
psi
|
93.76
|
Empey St.
|
Pressure
|
psi
|
82.65
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
Treatment Operators Analysis
Source | Parameter | Units | MAC | AO/OG | Minimum | Maximum | Average |
Grand River
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.03
|
0.22
|
0.09
|
Brantford POE
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.21
|
0.51
|
0.34
|
Grand River
|
True Colour
|
PtCo
|
Not applicable
|
Not applicable
|
11
|
27
|
17
|
Brantford POE
|
True Colour
|
PtCo
|
Not applicable
|
5
|
0.0
|
2
|
0.5
|
Brantford POE
|
Aluminum
|
mg/L
|
Not applicable
|
0.100
|
0.025
|
0.084
|
0.042
|
Grand River
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.121
|
0.190
|
0.144
|
Brantford POE
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.039
|
0.062
|
0.050
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
Not applicable
|
0.10
|
0.79
|
0.61
|
Brantford POE
|
Free chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
Not applicable
|
2.40
|
2.70
|
2.49
|
Brantford POE
|
Total Chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
2.50
|
2.80
|
2.59
|
Definitions:
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
April 2023 |
SCADA Data - Monthly Averages
Water Treatment Plant |
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
36.88
|
Brantford POE
|
Flow Rate
|
ML/d
|
30.21
|
Grand River
|
Turbidity
|
NTU
|
13.78
|
Filter 1
|
Turbidity
|
NTU
|
0.043
|
Filter 2
|
Turbidity
|
NTU
|
0.042
|
Filter 3
|
Turbidity
|
NTU
|
0.047
|
Filter 4
|
Turbidity
|
NTU
|
0.047
|
Filter 5
|
Turbidity
|
NTU
|
0.040
|
Filter 6
|
Turbidity
|
NTU
|
0.045
|
Filter 7
|
Turbidity
|
NTU
|
0.044
|
Filter 8
|
Turbidity
|
NTU
|
0.051
|
Brantford POE
|
Turbidity
|
NTU
|
0.055
|
CCC Effluent
|
Log Removal
|
Not applicable
|
13.48
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.53
|
Brantford POE
|
Pressure
|
psi
|
97.02
|
SCADA Data - Monthly Averages
Distribution System |
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.35
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.22
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.49
|
Albion St. Booster
|
Pressure
|
psi
|
90.78
|
Tollgate Reservoir
|
Pressure
|
psi
|
58.50
|
Park Rd. Reservoir
|
Pressure
|
psi
|
78.89
|
Northwest Reservoir
|
Pressure
|
psi
|
85.52
|
Bell Lane
|
Pressure
|
psi
|
50.66
|
Fifth Ave
|
Pressure
|
psi
|
96.20
|
Lawren Harris
|
Pressure
|
psi
|
64.68
|
St. Andrews
|
Pressure
|
psi
|
93.30
|
Empey St.
|
Pressure
|
psi
|
82.73
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
Treatment Operators Analysis
Source | Parameter | Units | MAC | AO/OG | Minimum | Maximum | Average |
Grand River
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.04
|
0.18
|
0.10
|
Brantford POE
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.27
|
0.58
|
0.37
|
Grand River
|
True Colour
|
PtCo
|
Not applicable
|
Not applicable
|
14
|
30
|
23
|
Brantford POE
|
True Colour
|
PtCo
|
Not applicable
|
5
|
0.0
|
0
|
0.58
|
Brantford POE
|
Aluminum
|
mg/L
|
Not applicable
|
0.100
|
0.016
|
0.098
|
0.045
|
Grand River
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.146
|
0.212
|
0.182
|
Brantford POE
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.023
|
0.062
|
0.047
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
Not applicable
|
0.08
|
0.74
|
0.40
|
Brantford POE
|
Free chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
Not applicable
|
2.40
|
2.80
|
2.55
|
Brantford POE
|
Total Chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
2.50
|
2.90
|
2.65
|
Definitions:
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
May 2023 |
SCADA Data - Monthly Averages
Water Treatment Plant |
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
39.58
|
Brantford POE
|
Flow Rate
|
ML/d
|
34.91
|
Grand River
|
Turbidity
|
NTU
|
5.99
|
Filter 1
|
Turbidity
|
NTU
|
0.036
|
Filter 2
|
Turbidity
|
NTU
|
0.036
|
Filter 3
|
Turbidity
|
NTU
|
0.036
|
Filter 4
|
Turbidity
|
NTU
|
0.040
|
Filter 5
|
Turbidity
|
NTU
|
0.036
|
Filter 6
|
Turbidity
|
NTU
|
0.041
|
Filter 7
|
Turbidity
|
NTU
|
0.039
|
Filter 8
|
Turbidity
|
NTU
|
0.042
|
Brantford POE
|
Turbidity
|
NTU
|
0.048
|
CCC Effluent
|
Log Removal
|
Not applicable
|
15.64
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.56
|
Brantford POE
|
Pressure
|
psi
|
97.23
|
SCADA Data - Monthly Averages
Distribution System |
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.22
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.19
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.41
|
Albion St. Booster
|
Pressure
|
psi
|
90.37
|
Tollgate Reservoir
|
Pressure
|
psi
|
59.16
|
Park Rd. Reservoir
|
Pressure
|
psi
|
78.59
|
Northwest Reservoir
|
Pressure
|
psi
|
84.64
|
Bell Lane
|
Pressure
|
psi
|
50.65
|
Fifth Ave
|
Pressure
|
psi
|
96.00
|
Lawren Harris
|
Pressure
|
psi
|
64.70
|
St. Andrews
|
Pressure
|
psi
|
92.40
|
Empey St.
|
Pressure
|
psi
|
82.31
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
Treatment Operators Analysis
Source | Parameter | Units | MAC | AO/OG | Minimum | Maximum | Average |
Grand River
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.03
|
0.14
|
0.09
|
Brantford POE
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.22
|
0.66
|
0.40
|
Grand River
|
True Colour
|
PtCo
|
Not applicable
|
Not applicable
|
14
|
27
|
21
|
Brantford POE
|
True Colour
|
PtCo
|
Not applicable
|
5
|
0
|
2
|
1
|
Brantford POE
|
Aluminum
|
mg/L
|
Not applicable
|
0.100
|
0.017
|
0.205
|
0.119
|
Grand River
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.136
|
0.255
|
0.168
|
Brantford POE
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.032
|
0.057
|
0.044
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
Not applicable
|
0.52
|
0.74
|
0.68
|
Brantford POE
|
Free chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
Not applicable
|
2.40
|
2.90
|
2.59
|
Brantford POE
|
Total Chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
2.50
|
3.00
|
2.69
|
Definitions:
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
June 2023 |
Water Treatment Plant
Source | Parameter | Units | Monthly Average |
Grand River
|
Flow Rate
|
ML/d
|
43.10
|
Brantford POE
|
Flow Rate
|
ML/d
|
38.44
|
Grand River
|
Turbidity
|
NTU
|
6.01
|
Filter 1
|
Turbidity
|
NTU
|
0.047
|
Filter 2
|
Turbidity
|
NTU
|
0.049
|
Filter 3
|
Turbidity
|
NTU
|
0.046
|
Filter 4
|
Turbidity
|
NTU
|
0.052
|
Filter 5
|
Turbidity
|
NTU
|
0.048
|
Filter 6
|
Turbidity
|
NTU
|
0.053
|
Filter 7
|
Turbidity
|
NTU
|
0.054
|
Filter 8
|
Turbidity
|
NTU
|
0.054
|
Brantford POE
|
Turbidity
|
NTU
|
0.061
|
CCC Effluent
|
Log Removal
|
Not applicable
|
19.72
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.60
|
Brantford POE
|
Pressure
|
psi
|
97.21
|
Distribution System
Source | Parameter | Units | Monthly Average |
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.11
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.08
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.41
|
Albion St. Booster
|
Pressure
|
psi
|
90.33
|
Tollgate Reservoir
|
Pressure
|
psi
|
59.50
|
Park Rd. Reservoir
|
Pressure
|
psi
|
78.61
|
Northwest Reservoir
|
Pressure
|
psi
|
84.73
|
Bell Lane
|
Pressure
|
psi
|
50.65
|
Fifth Ave
|
Pressure
|
psi
|
95.80
|
Lawren Harris
|
Pressure
|
psi
|
64.87
|
St. Andrews
|
Pressure
|
psi
|
91.78
|
Empey St.
|
Pressure
|
psi
|
82.32
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
Treatment Operators Analysis
Source | Parameter | Units | MAC | AO/OG | Minimum | Maximum | Average |
Grand River
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.04
|
0.17
|
0.11
|
Brantford POE
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.21
|
0.50
|
0.40
|
Grand River
|
True Colour
|
PtCo
|
Not applicable
|
Not applicable
|
13
|
23
|
19
|
Brantford POE
|
True Colour
|
PtCo
|
Not applicable
|
5
|
0
|
2
|
0
|
Brantford POE
|
Aluminum
|
mg/L
|
Not applicable
|
0.100
|
0.045
|
0.208
|
0.119
|
Grand River
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.130
|
0.157
|
0.140
|
Brantford POE
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.033
|
0.046
|
0.037
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
Not applicable
|
0.56
|
0.83
|
0.66
|
Brantford POE
|
Free chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
Not applicable
|
2.40
|
3.00
|
2.61
|
Brantford POE
|
Total Chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
2.50
|
3.10
|
2.71
|
|
July 2023 |
Water Treatment Plant
Source | Parameter | Units | Monthly Average |
Grand River
|
Flow Rate
|
ML/d
|
40.39
|
Brantford POE
|
Flow Rate
|
ML/d
|
36.63
|
Grand River
|
Turbidity
|
NTU
|
15.42
|
Filter 1
|
Turbidity
|
NTU
|
0.043
|
Filter 2
|
Turbidity
|
NTU
|
0.044
|
Filter 3
|
Turbidity
|
NTU
|
0.047
|
Filter 4
|
Turbidity
|
NTU
|
0.047
|
Filter 5
|
Turbidity
|
NTU
|
0.043
|
Filter 6
|
Turbidity
|
NTU
|
0.048
|
Filter 7
|
Turbidity
|
NTU
|
0.048
|
Filter 8
|
Turbidity
|
NTU
|
0.052
|
Brantford POE
|
Turbidity
|
NTU
|
0.053
|
CCC Effluent
|
Log Removal
|
Not applicable
|
27.26
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.61
|
Brantford POE
|
Pressure
|
psi
|
97.17
|
Distribution System
Source | Parameter | Units | Monthly Average |
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.12
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
1.93
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.41
|
Albion St. Booster
|
Pressure
|
psi
|
90.29
|
Tollgate Reservoir
|
Pressure
|
psi
|
59.05
|
Park Rd. Reservoir
|
Pressure
|
psi
|
78.41
|
Northwest Reservoir
|
Pressure
|
psi
|
84.37
|
Bell Lane
|
Pressure
|
psi
|
50.51
|
Fifth Ave
|
Pressure
|
psi
|
95.84
|
Lawren Harris
|
Pressure
|
psi
|
64.68
|
St. Andrews
|
Pressure
|
psi
|
91.90
|
Empey St.
|
Pressure
|
psi
|
82.15
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
Treatment Operators Analysis
Source | Parameter | Units | MAC | AO/OG | Minimum | Maximum | Average |
Grand River
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.04
|
0.21
|
0.12
|
Brantford POE
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.24
|
0.56
|
0.42
|
Grand River
|
True Colour
|
PtCo
|
Not applicable
|
Not applicable
|
13
|
35
|
22
|
Brantford POE
|
True Colour
|
PtCo
|
Not applicable
|
5
|
0
|
2
|
0
|
Brantford POE
|
Aluminum
|
mg/L
|
Not applicable
|
0.100
|
0.057
|
0.173
|
0.130
|
Grand River
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.148
|
0.220
|
0.173
|
Brantford POE
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.034
|
0.058
|
0.044
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
Not applicable
|
0.54
|
0.75
|
0.63
|
Brantford POE
|
Free chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
Not applicable
|
2.40
|
2.80
|
2.61
|
Brantford POE
|
Total Chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
2.50
|
2.90
|
2.71
|
Definitions:
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
August 2023 |
Water Treatment Plant
Source | Parameter | Units | Monthly Average |
Grand River
|
Flow Rate
|
ML/d
|
38.91
|
Brantford POE
|
Flow Rate
|
ML/d
|
34.60
|
Grand River
|
Turbidity
|
NTU
|
5.02
|
Filter 1
|
Turbidity
|
NTU
|
0.040
|
Filter 2
|
Turbidity
|
NTU
|
0.038
|
Filter 3
|
Turbidity
|
NTU
|
0.046
|
Filter 4
|
Turbidity
|
NTU
|
0.043
|
Filter 5
|
Turbidity
|
NTU
|
0.041
|
Filter 6
|
Turbidity
|
NTU
|
0.046
|
Filter 7
|
Turbidity
|
NTU
|
0.043
|
Filter 8
|
Turbidity
|
NTU
|
0.051
|
Brantford POE
|
Turbidity
|
NTU
|
0.049
|
CCC Effluent
|
Log Removal
|
Not applicable
|
23.11
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.62
|
Brantford POE
|
Pressure
|
psi
|
96.99
|
Distribution System
Source | Parameter | Units | Monthly Average |
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.18
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.02
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.37
|
Albion St. Booster
|
Pressure
|
psi
|
90.27
|
Tollgate Reservoir
|
Pressure
|
psi
|
58.50
|
Park Rd. Reservoir
|
Pressure
|
psi
|
78.62
|
Northwest Reservoir
|
Pressure
|
psi
|
84.63
|
Bell Lane
|
Pressure
|
psi
|
50.58
|
Fifth Ave
|
Pressure
|
psi
|
95.90
|
Lawren Harris
|
Pressure
|
psi
|
64.44
|
St. Andrews
|
Pressure
|
psi
|
91.79
|
Empey St.
|
Pressure
|
psi
|
82.72
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
Treatment Operators Analysis
Source | Parameter | Units | MAC | AO/OG | Minimum | Maximum | Average |
Grand River
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.05
|
0.21
|
0.11
|
Brantford POE
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.31
|
0.50
|
0.40
|
Grand River
|
True Colour
|
PtCo
|
Not applicable
|
Not applicable
|
15
|
30
|
21.7
|
Brantford POE
|
True Colour
|
PtCo
|
Not applicable
|
5
|
0
|
2
|
0.50
|
Brantford POE
|
Aluminum
|
mg/L
|
Not applicable
|
0.100
|
0.044
|
0.182
|
0.137
|
Grand River
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.154
|
0.229
|
0.181
|
Brantford POE
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.040
|
0.066
|
0.049
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
Not applicable
|
0.51
|
0.83
|
0.67
|
Brantford POE
|
Free chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
Not applicable
|
2.40
|
2.80
|
2.61
|
Brantford POE
|
Total Chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
2.50
|
2.90
|
2.71
|
Definitions:
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
September 2023 |
Scada Data Monthly Averages
Water Treatment Plant |
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
39.06
|
Brantford POE
|
Flow Rate
|
ML/d
|
35.14
|
Grand River
|
Turbidity
|
NTU
|
4.06
|
Filter 1
|
Turbidity
|
NTU
|
0.040
|
Filter 2
|
Turbidity
|
NTU
|
0.038
|
Filter 3
|
Turbidity
|
NTU
|
0.045
|
Filter 4
|
Turbidity
|
NTU
|
0.048
|
Filter 5
|
Turbidity
|
NTU
|
0.040
|
Filter 6
|
Turbidity
|
NTU
|
0.048
|
Filter 7
|
Turbidity
|
NTU
|
0.043
|
Filter 8
|
Turbidity
|
NTU
|
0.051
|
Brantford POE
|
Turbidity
|
NTU
|
0.052
|
CCC Effluent
|
Log Removal
|
Not applicable
|
19.94
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.60
|
Brantford POE
|
Pressure
|
psi
|
97.15
|
Scada Data Monthly Averages
Distribution System |
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.22
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.02
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.46
|
Albion St. Booster
|
Pressure
|
psi
|
90.44
|
Tollgate Reservoir
|
Pressure
|
psi
|
58.96
|
Park Rd. Reservoir
|
Pressure
|
psi
|
78.73
|
Northwest Reservoir
|
Pressure
|
psi
|
84.12
|
Bell Lane
|
Pressure
|
psi
|
50.69
|
Fifth Ave
|
Pressure
|
psi
|
96.07
|
Lawren Harris
|
Pressure
|
psi
|
64.80
|
St. Andrews
|
Pressure
|
psi
|
91.92
|
Empey St.
|
Pressure
|
psi
|
82.48
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
Treatment Operators Analysis
Source | Parameter | Units | MAC | AO/OG | Minimum | Maximum | Average |
Grand River
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.03
|
0.13
|
0.08
|
Brantford POE
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.29
|
0.66
|
0.41
|
Grand River
|
True Colour
|
PtCo
|
Not applicable
|
Not applicable
|
12
|
21
|
17
|
Brantford POE
|
True Colour
|
PtCo
|
Not applicable
|
5
|
0
|
1
|
0
|
Brantford POE
|
Aluminum
|
mg/L
|
Not applicable
|
0.100
|
0.091
|
0.191
|
0.152
|
Grand River
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.127
|
0.168
|
0.144
|
Brantford POE
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.035
|
0.052
|
0.041
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
Not applicable
|
0.44
|
0.88
|
0.65
|
Brantford POE
|
Free chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
Not applicable
|
2.40
|
2.80
|
2.59
|
Brantford POE
|
Total Chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
2.50
|
2.90
|
2.69
|
Definitions:
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
October 2023 |
Scada Data Monthly Averages
Water Treatment Plant |
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
38.12
|
Brantford POE
|
Flow Rate
|
ML/d
|
32.66
|
Grand River
|
Turbidity
|
NTU
|
3.82
|
Filter 1
|
Turbidity
|
NTU
|
0.045
|
Filter 2
|
Turbidity
|
NTU
|
0.043
|
Filter 3
|
Turbidity
|
NTU
|
0.046
|
Filter 4
|
Turbidity
|
NTU
|
0.052
|
Filter 5
|
Turbidity
|
NTU
|
0.044
|
Filter 6
|
Turbidity
|
NTU
|
0.049
|
Filter 7
|
Turbidity
|
NTU
|
0.045
|
Filter 8
|
Turbidity
|
NTU
|
0.052
|
Brantford POE
|
Turbidity
|
NTU
|
0.056
|
CCC Effluent
|
Log Removal
|
Not applicable
|
16.07
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.59
|
Brantford POE
|
Pressure
|
psi
|
97.13
|
SCADA Data Monthly Averages
Distribution System |
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.10
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.09
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.49
|
Albion St. Booster
|
Pressure
|
psi
|
90.42
|
Tollgate Reservoir
|
Pressure
|
psi
|
58.46
|
Park Rd. Reservoir
|
Pressure
|
psi
|
78.63
|
Northwest Reservoir
|
Pressure
|
psi
|
83.88
|
Bell Lane
|
Pressure
|
psi
|
50.75
|
Fifth Ave
|
Pressure
|
psi
|
96.20
|
Lawren Harris
|
Pressure
|
psi
|
64.55
|
St. Andrews
|
Pressure
|
psi
|
92.68
|
Empey St.
|
Pressure
|
psi
|
82.31
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
Treatment Operators Analysis
Source | Parameter | Units | MAC | AO/OG | Minimum | Maximum | Average |
Grand River
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.03
|
0.14
|
0.08
|
Brantford POE
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.23
|
0.56
|
0.36
|
Grand River
|
True Colour
|
PtCo
|
Not applicable
|
Not applicable
|
11
|
23
|
15.35
|
Brantford POE
|
True Colour
|
PtCo
|
Not applicable
|
5
|
0
|
1
|
0
|
Brantford POE
|
Aluminum
|
mg/L
|
Not applicable
|
0.100
|
0.053
|
0.193
|
0.123
|
Grand River
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.116
|
0.149
|
0.129
|
Brantford POE
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.034
|
0.045
|
0.038
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
Not applicable
|
0.55
|
0.76
|
0.66
|
Brantford POE
|
Free chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
Not applicable
|
2.30
|
2.80
|
2.58
|
Brantford POE
|
Total Chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
2.40
|
2.90
|
2.68
|
Definitions:
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
November 2023 |
SCADA Data - Monthly Averages
Water Treatment Plant |
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
37.41
|
Brantford POE
|
Flow Rate
|
ML/d
|
31.00
|
Grand River
|
Turbidity
|
NTU
|
2.99
|
Filter 1
|
Turbidity
|
NTU
|
0.032
|
Filter 2
|
Turbidity
|
NTU
|
0.030
|
Filter 3
|
Turbidity
|
NTU
|
0.034
|
Filter 4
|
Turbidity
|
NTU
|
0.037
|
Filter 5
|
Turbidity
|
NTU
|
0.031
|
Filter 6
|
Turbidity
|
NTU
|
0.036
|
Filter 7
|
Turbidity
|
NTU
|
0.033
|
Filter 8
|
Turbidity
|
NTU
|
0.038
|
Brantford POE
|
Turbidity
|
NTU
|
0.041
|
CCC Effluent
|
Log Removal
|
Not applicable
|
10.37
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.57
|
Brantford POE
|
Pressure
|
psi
|
97.12
|
SCADA Data - Monthly Averages
Distribution System |
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.47
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.36
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.57
|
Albion St. Booster
|
Pressure
|
psi
|
90.78
|
Tollgate Reservoir
|
Pressure
|
psi
|
58.65
|
Park Rd. Reservoir
|
Pressure
|
psi
|
78.89
|
Northwest Reservoir
|
Pressure
|
psi
|
84.34
|
Bell Lane
|
Pressure
|
psi
|
50.86
|
Fifth Ave
|
Pressure
|
psi
|
96.36
|
Lawren Harris
|
Pressure
|
psi
|
64.91
|
St. Andrews
|
Pressure
|
psi
|
93.40
|
Empey St.
|
Pressure
|
psi
|
82.70
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
Treatment Operators Analysis
Source | Parameter | Units | MAC | AO/OG | Minimum | Maximum | Average |
Grand River
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.01
|
0.11
|
0.07
|
Brantford POE
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.16
|
0.44
|
0.32
|
Grand River
|
True Colour
|
PtCo
|
Not applicable
|
Not applicable
|
12
|
32
|
15.5
|
Brantford POE
|
True Colour
|
PtCo
|
Not applicable
|
5
|
0
|
2
|
0.35
|
Brantford POE
|
Aluminum
|
mg/L
|
Not applicable
|
0.100
|
0.046
|
0.136
|
0.089
|
Grand River
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.116
|
0.165
|
0.128
|
Brantford POE
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.037
|
0.057
|
0.046
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
Not applicable
|
0.59
|
0.82
|
0.69
|
Brantford POE
|
Free chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
Not applicable
|
2.40
|
2.80
|
2.57
|
Brantford POE
|
Total Chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
2.50
|
2.90
|
2.67
|
Definitions:
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
December 2023 |
SCADA Data - Monthly Averages
Water Treatment Plant |
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
36.57
|
Brantford POE
|
Flow Rate
|
ML/d
|
30.36
|
Grand River
|
Turbidity
|
NTU
|
4.24
|
Filter 1
|
Turbidity
|
NTU
|
0.030
|
Filter 2
|
Turbidity
|
NTU
|
0.030
|
Filter 3
|
Turbidity
|
NTU
|
0.034
|
Filter 4
|
Turbidity
|
NTU
|
0.036
|
Filter 5
|
Turbidity
|
NTU
|
0.030
|
Filter 6
|
Turbidity
|
NTU
|
0.034
|
Filter 7
|
Turbidity
|
NTU
|
0.033
|
Filter 8
|
Turbidity
|
NTU
|
0.036
|
Brantford POE
|
Turbidity
|
NTU
|
0.037
|
CCC Effluent
|
Log Removal
|
Not applicable
|
9.40
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.55
|
Brantford POE
|
Pressure
|
psi
|
97.11
|
SCADA Data - Monthly Averages
Distribution System |
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.41
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.38
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.47
|
Albion St. Booster
|
Pressure
|
psi
|
90.74
|
Tollgate Reservoir
|
Pressure
|
psi
|
58.42
|
Park Rd. Reservoir
|
Pressure
|
psi
|
78.84
|
Northwest Reservoir
|
Pressure
|
psi
|
84.63
|
Bell Lane
|
Pressure
|
psi
|
50.87
|
Fifth Ave
|
Pressure
|
psi
|
96.48
|
Lawren Harris
|
Pressure
|
psi
|
64.74
|
St. Andrews
|
Pressure
|
psi
|
93.35
|
Empey St.
|
Pressure
|
psi
|
82.67
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
Treatment Operators Analysis
Source | Parameter | Units | MAC | AO/OG | Minimum | Maximum | Average |
Grand River
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.01
|
0.16
|
0.07
|
Brantford POE
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.22
|
0.43
|
0.33
|
Grand River
|
True Colour
|
PtCo
|
Not applicable
|
Not applicable
|
12
|
26
|
16.46
|
Brantford POE
|
True Colour
|
PtCo
|
Not applicable
|
5
|
0
|
2
|
0.65
|
Brantford POE
|
Aluminum
|
mg/L
|
Not applicable
|
0.100
|
0.036
|
0.121
|
0.082
|
Grand River
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.119
|
0.189
|
0.138
|
Brantford POE
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.047
|
0.063
|
0.055
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
Not applicable
|
0.53
|
0.80
|
0.67
|
Brantford POE
|
Free chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
Not applicable
|
2.40
|
2.80
|
2.54
|
Brantford POE
|
Total Chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
2.50
|
2.90
|
2.64
|
Definitions:
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|