January 2022 |
Treatment Operators Analysis
Source | Parameter | Units | MAC | AO/OG | Minimum | Maximum | Average |
Grand River |
Ammonia |
mg/L |
Not applicable |
Not applicable |
0.03 |
0.16 |
0.08 |
Brantford POE |
Ammonia |
mg/L |
Not applicable |
Not applicable |
0.17 |
0.44 |
0.32 |
Grand River |
True Colour |
PtCo |
Not applicable |
Not applicable |
7.0 |
19.0 |
14.0 |
Brantford POE |
True Colour |
PtCo |
Not applicable |
5 |
0.0 |
1.0 |
0.0 |
Brantford POE |
Aluminum |
mg/L |
Not applicable |
0.100 |
0.022 |
0.062 |
0.045 |
Grand River |
UV254 |
Not applicable |
Not applicable |
Not applicable |
0.110 |
0.157 |
0.129 |
Brantford POE |
UV254 |
Not applicable |
Not applicable |
Not applicable |
0.048 |
0.066 |
0.055 |
Brantford POE |
Fluoride |
mg/L |
1.50 |
Not applicable |
0.630 |
0.800 |
0.730 |
Brantford POE |
Free chlorine |
mg/L |
Not applicable |
Not applicable |
0.10 |
0.10 |
0.10 |
Brantford POE |
Combined Chlorine |
mg/L |
3.00 |
Not applicable |
2.40 |
2.90 |
2.60 |
Brantford POE |
Total Chlorine |
mg/L |
Not applicable |
Not applicable |
2.50 |
3.00 |
2.70
|
Definitions:
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
SCADA Data - Monthly Averages
Water Treatment Plant |
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
34.54
|
Brantford POE
|
Flow Rate
|
ML/d
|
31.55
|
Grand River
|
Turbidity
|
NTU
|
2.28
|
Filter 1
|
Turbidity
|
NTU
|
0.025
|
Filter 2
|
Turbidity
|
NTU
|
0.023
|
Filter 3
|
Turbidity
|
NTU
|
0.025
|
Filter 4
|
Turbidity
|
NTU
|
0.029
|
Filter 5
|
Turbidity
|
NTU
|
0.024
|
Filter 6
|
Turbidity
|
NTU
|
0.033
|
Filter 7
|
Turbidity
|
NTU
|
0.031
|
Filter 8
|
Turbidity
|
NTU
|
0.032
|
Brantford POE
|
Turbidity
|
NTU
|
0.028
|
CCC Effluent
|
Log Removal
|
Not applicable
|
8.21
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.57
|
Brantford POE
|
Pressure
|
psi
|
97.05
|
SCADA Data - Monthly Averages
Distribution System |
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.49
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.49
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.64
|
Albion St. Booster
|
Pressure
|
psi
|
90.92
|
Tollgate Reservoir
|
Pressure
|
psi
|
58.45
|
Park Rd. Reservoir
|
Pressure
|
psi
|
78.93
|
Northwest Reservoir
|
Pressure
|
psi
|
85.73
|
Bell Lane
|
Pressure
|
psi
|
50.74
|
Fifth Ave
|
Pressure
|
psi
|
96.29
|
Lawren Harris
|
Pressure
|
psi
|
64.67
|
St. Andrews
|
Pressure
|
psi
|
93.15
|
Empey St.
|
Pressure
|
psi
|
82.50
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
February 2022 |
Treatment Operators Analysis
Source | Parameter | Units | MAC | AO/OG | Minimum | Maximum | Average |
Grand River
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.03
|
0.45
|
0.16
|
Brantford POE
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.22
|
0.48
|
0.35
|
Grand River
|
True Colour
|
PtCo
|
Not applicable
|
Not applicable
|
8
|
28
|
17
|
Brantford POE
|
True Colour
|
PtCo
|
Not applicable
|
5
|
0.0
|
2.0
|
0.5
|
Brantford POE
|
Aluminum
|
mg/L
|
Not applicable
|
0.100
|
0.019
|
0.075
|
0.043
|
Grand River
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.103
|
0.166
|
0.126
|
Brantford POE
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.035
|
0.052
|
0.046
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
Not applicable
|
0.54
|
0.79
|
0.69
|
Brantford POE
|
Free chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
Not applicable
|
2.40
|
2.80
|
2.57
|
Brantford POE
|
Total Chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
2.50
|
2.90
|
2.67
|
Definitions:
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
SCADA Data - Monthly Averages
Water Treatment Plant |
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
37.20
|
Brantford POE
|
Flow Rate
|
ML/d
|
32.42
|
Grand River
|
Turbidity
|
NTU
|
4.95
|
Filter 1
|
Turbidity
|
NTU
|
0.029
|
Filter 2
|
Turbidity
|
NTU
|
0.026
|
Filter 3
|
Turbidity
|
NTU
|
0.030
|
Filter 4
|
Turbidity
|
NTU
|
0.032
|
Filter 5
|
Turbidity
|
NTU
|
0.027
|
Filter 6
|
Turbidity
|
NTU
|
0.033
|
Filter 7
|
Turbidity
|
NTU
|
0.037
|
Filter 8
|
Turbidity
|
NTU
|
0.034
|
Brantford POE
|
Turbidity
|
NTU
|
0.031
|
CCC Effluent
|
Log Removal
|
Not applicable
|
8.69
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.56
|
Brantford POE
|
Pressure
|
psi
|
97.016
|
SCADA Data - Monthly Averages
Distribution Center |
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.44
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.59
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.63
|
Albion St. Booster
|
Pressure
|
psi
|
90.96
|
Tollgate Reservoir
|
Pressure
|
psi
|
58.60
|
Park Rd. Reservoir
|
Pressure
|
psi
|
78.96
|
Northwest Reservoir
|
Pressure
|
psi
|
86.28
|
Bell Lane
|
Pressure
|
psi
|
50.79
|
Fifth Ave
|
Pressure
|
psi
|
96.30
|
Lawren Harris
|
Pressure
|
psi
|
64.70
|
St. Andrews
|
Pressure
|
psi
|
93.23
|
Empey St.
|
Pressure
|
psi
|
82.49
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
March 2022 |
Treatment Operators Analysis
Source | Parameter | Units | MAC | AO/OG | Minimum | Maximum | Average |
Grand River
|
Ammonia
|
mg/L
|
|
|
0.06
|
0.35
|
0.14
|
Brantford POE
|
Ammonia
|
mg/L
|
|
|
0.25
|
0.50
|
0.36
|
Grand River
|
True Colour
|
PtCo
|
|
|
12
|
25
|
21
|
Brantford POE
|
True Colour
|
PtCo
|
|
5
|
0
|
2
|
0.40
|
Brantford POE
|
Aluminum
|
mg/L
|
|
0.100
|
0.017
|
0.062
|
0.036
|
Grand River
|
UV254
|
|
|
|
0.139
|
0.179
|
0.158
|
Brantford POE
|
UV254
|
|
|
|
0.029
|
0.059
|
0.048
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
|
0.37
|
0.87
|
0.66
|
Brantford POE
|
Free chlorine
|
mg/L
|
|
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
|
2.40
|
2.80
|
2.59
|
Brantford POE
|
Total Chlorine
|
mg/L
|
|
|
2.50
|
2.90
|
2.69
|
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
SCADA Data - Monthly Averages
Water Treatment Plant |
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
37.32
|
Brantford POE
|
Flow Rate
|
ML/d
|
31.32
|
|
|
|
|
Grand River
|
Turbidity
|
NTU
|
10.69
|
Filter 1
|
Turbidity
|
NTU
|
0.035
|
Filter 2
|
Turbidity
|
NTU
|
0.032
|
Filter 3
|
Turbidity
|
NTU
|
0.035
|
Filter 4
|
Turbidity
|
NTU
|
0.038
|
Filter 5
|
Turbidity
|
NTU
|
0.033
|
Filter 6
|
Turbidity
|
NTU
|
0.039
|
Filter 7
|
Turbidity
|
NTU
|
0.044
|
Filter 8
|
Turbidity
|
NTU
|
0.041
|
Brantford POE
|
Turbidity
|
NTU
|
0.038
|
CCC Effluent
|
Log Removal
|
|
9.04
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.55
|
Brantford POE
|
Pressure
|
psi
|
97.01
|
SCADA Data - Monthly Averages
Distribution System |
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.46
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.48
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.63
|
Albion St. Booster
|
Pressure
|
psi
|
91.07
|
Tollgate Reservoir
|
Pressure
|
psi
|
58.69
|
Park Rd. Reservoir
|
Pressure
|
psi
|
79.05
|
Northwest Reservoir
|
Pressure
|
psi
|
85.43
|
Bell Lane
|
Pressure
|
psi
|
50.67
|
Fifth Ave
|
Pressure
|
psi
|
96.33
|
Lawren Harris
|
Pressure
|
psi
|
64.85
|
St. Andrews
|
Pressure
|
psi
|
93.19
|
Empey St.
|
Pressure
|
psi
|
82.52
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
April 2022 |
Treatment Operators Analysis
Source | Parameter | Units | MAC | AO/OG | Minimum | Maximum | Average |
Grand River
|
Ammonia
|
mg/L
|
|
|
0.02
|
0.17
|
0.07
|
Brantford POE
|
Ammonia
|
mg/L
|
|
|
0.23
|
0.53
|
0.35
|
Grand River
|
True Colour
|
PtCo
|
|
|
14
|
21
|
18
|
Brantford POE
|
True Colour
|
PtCo
|
|
5
|
0
|
2
|
0.36
|
Brantford POE
|
Aluminum
|
mg/L
|
|
0.100
|
0.026
|
0.161
|
0.098
|
Grand River
|
UV254
|
|
|
|
0.127
|
0.153
|
0.140
|
Brantford POE
|
UV254
|
|
|
|
0.034
|
0.054
|
0.044
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
|
0.22
|
0.81
|
0.59
|
Brantford POE
|
Free chlorine
|
mg/L
|
|
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
|
2.30
|
2.80
|
2.61
|
Brantford POE
|
Total Chlorine
|
mg/L
|
|
|
2.40
|
2.90
|
2.71
|
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
SCADA Data - Monthly Averages
Water Treatment Plant |
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
36.72
|
Brantford POE
|
Flow Rate
|
ML/d
|
29.67
|
Grand River
|
Turbidity
|
NTU
|
8.14
|
Filter 1
|
Turbidity
|
NTU
|
0.040
|
Filter 2
|
Turbidity
|
NTU
|
0.038
|
Filter 3
|
Turbidity
|
NTU
|
0.044
|
Filter 4
|
Turbidity
|
NTU
|
0.050
|
Filter 5
|
Turbidity
|
NTU
|
0.042
|
Filter 6
|
Turbidity
|
NTU
|
0.050
|
Filter 7
|
Turbidity
|
NTU
|
0.052
|
Filter 8
|
Turbidity
|
NTU
|
0.049
|
Brantford POE
|
Turbidity
|
NTU
|
0.049
|
CCC Effluent
|
Log Removal
|
|
10.90
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.58
|
Brantford POE
|
Pressure
|
psi
|
96.97
|
SCADA Data - Monthly Averages
Distribution System |
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.34
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.28
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.64
|
Albion St. Booster
|
Pressure
|
psi
|
91.30
|
Tollgate Reservoir
|
Pressure
|
psi
|
59.18
|
Park Rd. Reservoir
|
Pressure
|
psi
|
79.25
|
Northwest Reservoir
|
Pressure
|
psi
|
85.78
|
Bell Lane
|
Pressure
|
psi
|
50.71
|
Fifth Ave
|
Pressure
|
psi
|
96.42
|
Lawren Harris
|
Pressure
|
psi
|
65.77
|
St. Andrews
|
Pressure
|
psi
|
92.84
|
Empey St.
|
Pressure
|
psi
|
83.08
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
May 2022 |
Treatment Operators Analysis
Source | Parameter | Units | MAC | AO/OG | Minimum | Maximum | Average |
Grand River
|
Ammonia
|
mg/L
|
|
|
0.04
|
0.17
|
0.08
|
Brantford POE
|
Ammonia
|
mg/L
|
|
|
0.24
|
0.51
|
0.38
|
Grand River
|
True Colour
|
PtCo
|
|
|
15
|
24
|
18.3
|
Brantford POE
|
True Colour
|
PtCo
|
|
5
|
0
|
2
|
0.36
|
Brantford POE
|
Aluminum
|
mg/L
|
|
0.100
|
0.055
|
0.236
|
0.142
|
Grand River
|
UV254
|
|
|
|
0.129
|
0.181
|
0.142
|
Brantford POE
|
UV254
|
|
|
|
0.031
|
0.053
|
0.039
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
|
0.44
|
0.70
|
0.61
|
Brantford POE
|
Free chlorine
|
mg/L
|
|
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
|
2.40
|
2.90
|
2.60
|
Brantford POE
|
Total Chlorine
|
mg/L
|
|
|
2.50
|
3.00
|
2.70
|
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
SCADA Data Monthly Averages
Water Treatment Plant |
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
38.22
|
Brantford POE
|
Flow Rate
|
ML/d
|
33.28
|
Grand River
|
Turbidity
|
NTU
|
6.29
|
Filter 1
|
Turbidity
|
NTU
|
0.046
|
Filter 2
|
Turbidity
|
NTU
|
0.043
|
Filter 3
|
Turbidity
|
NTU
|
0.048
|
Filter 4
|
Turbidity
|
NTU
|
0.059
|
Filter 5
|
Turbidity
|
NTU
|
0.049
|
Filter 6
|
Turbidity
|
NTU
|
0.061
|
Filter 7
|
Turbidity
|
NTU
|
0.059
|
Filter 8
|
Turbidity
|
NTU
|
0.055
|
Brantford POE
|
Turbidity
|
NTU
|
0.057
|
CCC Effluent
|
Log Removal
|
|
16.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.60
|
Brantford POE
|
Pressure
|
psi
|
97.01
|
SCADA Data Monthly Averages
Distribution System |
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.26
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.19
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.61
|
Albion St. Booster
|
Pressure
|
psi
|
91.07
|
Tollgate Reservoir
|
Pressure
|
psi
|
59.15
|
Park Rd. Reservoir
|
Pressure
|
psi
|
79.13
|
Northwest Reservoir
|
Pressure
|
psi
|
86.22
|
Bell Lane
|
Pressure
|
psi
|
50.66
|
Fifth Ave
|
Pressure
|
psi
|
96.13
|
Lawren Harris
|
Pressure
|
psi
|
64.92
|
St. Andrews
|
Pressure
|
psi
|
92.12
|
Empey St.
|
Pressure
|
psi
|
82.92
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
June 2022 |
Treatment Operators Analysis
Source | Parameter | Units | MAC | AO/OG | Minimum | Maximum | Average |
Grand River
|
Ammonia
|
mg/L
|
|
|
0.02
|
0.14
|
0.09
|
Brantford POE
|
Ammonia
|
mg/L
|
|
|
0.29
|
0.60
|
0.40
|
Grand River
|
True Colour
|
PtCo
|
|
|
14
|
23
|
18
|
Brantford POE
|
True Colour
|
PtCo
|
|
5
|
0
|
2
|
0
|
Brantford POE
|
Aluminum
|
mg/L
|
|
0.100
|
0.030
|
0.203
|
0.098
|
Grand River
|
UV254
|
|
|
|
0.127
|
0.150
|
0.137
|
Brantford POE
|
UV254
|
|
|
|
|
|
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
|
0.45
|
0.72
|
0.63
|
Brantford POE
|
Free chlorine
|
mg/L
|
|
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
|
2.40
|
2.90
|
2.62
|
Brantford POE
|
Total Chlorine
|
mg/L
|
|
|
2.50
|
3.00
|
2.72
|
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
SCADA Data - Monthly Averages
Water Treatment Plant |
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
43.41
|
Brantford POE
|
Flow Rate
|
ML/d
|
37.75
|
Grand River
|
Turbidity
|
NTU
|
6.34
|
Filter 1
|
Turbidity
|
NTU
|
0.049
|
Filter 2
|
Turbidity
|
NTU
|
0.047
|
Filter 3
|
Turbidity
|
NTU
|
0.051
|
Filter 4
|
Turbidity
|
NTU
|
0.064
|
Filter 5
|
Turbidity
|
NTU
|
0.056
|
Filter 6
|
Turbidity
|
NTU
|
0.066
|
Filter 7
|
Turbidity
|
NTU
|
0.065
|
Filter 8
|
Turbidity
|
NTU
|
0.062
|
Brantford POE
|
Turbidity
|
NTU
|
0.059
|
CCC Effluent
|
Log Removal
|
|
21.72
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.62
|
Brantford POE
|
Pressure
|
psi
|
97.17
|
SCADA Data - Monthly Averages
Distribution System |
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.15
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.15
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.61
|
Albion St. Booster
|
Pressure
|
psi
|
90.32
|
Tollgate Reservoir
|
Pressure
|
psi
|
59.18
|
Park Rd. Reservoir
|
Pressure
|
psi
|
78.42
|
Northwest Reservoir
|
Pressure
|
psi
|
86.64
|
Bell Lane
|
Pressure
|
psi
|
50.56
|
Fifth Ave
|
Pressure
|
psi
|
95.89
|
Lawren Harris
|
Pressure
|
psi
|
64.48
|
St. Andrews
|
Pressure
|
psi
|
91.29
|
Empey St.
|
Pressure
|
psi
|
82.10
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
July 2022 |
Treatment Operators Analysis
Source | Parameter | Units | MAC | AO/OG | Minimum | Maximum | Average |
Grand River
|
Ammonia
|
mg/L
|
|
|
0.03
|
0.18
|
0.09
|
Brantford POE
|
Ammonia
|
mg/L
|
|
|
0.31
|
0.57
|
0.42
|
Grand River
|
True Colour
|
PtCo
|
|
|
11
|
23
|
16.46
|
Brantford POE
|
True Colour
|
PtCo
|
|
5
|
0
|
2
|
0.13
|
Brantford POE
|
Aluminum
|
mg/L
|
|
0.100
|
0.034
|
0.119
|
0.081
|
Grand River
|
UV254
|
|
|
|
0.123
|
0.142
|
0.129
|
Brantford POE
|
UV254
|
|
|
|
0.028
|
0.038
|
0.033
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
|
0.54
|
0.80
|
0.67
|
Brantford POE
|
Free chlorine
|
mg/L
|
|
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
|
2.40
|
2.90
|
2.65
|
Brantford POE
|
Total Chlorine
|
mg/L
|
|
|
2.50
|
3.00
|
2.75
|
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
SCADA Data - Monthly Averages
Water Treatment |
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
43.13
|
Brantford POE
|
Flow Rate
|
ML/d
|
39.26
|
Grand River
|
Turbidity
|
NTU
|
5.30
|
Filter 1
|
Turbidity
|
NTU
|
0.038
|
Filter 2
|
Turbidity
|
NTU
|
0.037
|
Filter 3
|
Turbidity
|
NTU
|
0.043
|
Filter 4
|
Turbidity
|
NTU
|
0.052
|
Filter 5
|
Turbidity
|
NTU
|
0.043
|
Filter 6
|
Turbidity
|
NTU
|
0.054
|
Filter 7
|
Turbidity
|
NTU
|
0.050
|
Filter 8
|
Turbidity
|
NTU
|
0.050
|
Brantford POE
|
Turbidity
|
NTU
|
0.048
|
CCC Effluent
|
Log Removal
|
|
26.09
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.63
|
Brantford POE
|
Pressure
|
psi
|
97.19
|
SCADA Data - Monthly Averages
Distribution System |
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.18
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.07
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.55
|
Albion St. Booster
|
Pressure
|
psi
|
90.33
|
Tollgate Reservoir
|
Pressure
|
psi
|
59.36
|
Park Rd. Reservoir
|
Pressure
|
psi
|
78.70
|
Northwest Reservoir
|
Pressure
|
psi
|
86.04
|
Bell Lane
|
Pressure
|
psi
|
50.48
|
Fifth Ave
|
Pressure
|
psi
|
95.67
|
Lawren Harris
|
Pressure
|
psi
|
64.57
|
St. Andrews
|
Pressure
|
psi
|
91.00
|
Empey St.
|
Pressure
|
psi
|
82.31
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
August 2022 |
Treatment Operators Analysis
Source | Parameter | Units | MAC | AO/OG | Minimum | Maximum | Average |
Grand River
|
Ammonia
|
mg/L
|
|
|
0.03
|
0.16
|
0.08
|
Brantford POE
|
Ammonia
|
mg/L
|
|
|
0.29
|
0.53
|
0.41
|
|
|
|
|
|
|
|
|
Grand River
|
True Colour
|
PtCo
|
|
|
10
|
19
|
15
|
Brantford POE
|
True Colour
|
PtCo
|
|
5
|
0
|
1
|
0.20
|
|
|
|
|
|
|
|
|
Brantford POE
|
Aluminum
|
mg/L
|
|
0.100
|
0.073
|
0.190
|
0.130
|
|
|
|
|
|
|
|
|
Grand River
|
UV254
|
|
|
|
0.122
|
0.140
|
0.130
|
Brantford POE
|
UV254
|
|
|
|
0.029
|
0.045
|
0.035
|
|
|
|
|
|
|
|
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
|
0.52
|
0.79
|
0.71
|
|
|
|
|
|
|
|
|
Brantford POE
|
Free chlorine
|
mg/L
|
|
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
|
2.50
|
2.80
|
2.65
|
Brantford POE
|
Total Chlorine
|
mg/L
|
|
|
2.60
|
2.90
|
2.75
|
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
SCADA Data - Monthly Averages
Water Treatment Plant |
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
42.49
|
Brantford POE
|
Flow Rate
|
ML/d
|
37.94
|
Grand River
|
Turbidity
|
NTU
|
5.17
|
Filter 1
|
Turbidity
|
NTU
|
0.036
|
Filter 2
|
Turbidity
|
NTU
|
0.035
|
Filter 3
|
Turbidity
|
NTU
|
0.041
|
Filter 4
|
Turbidity
|
NTU
|
0.050
|
Filter 5
|
Turbidity
|
NTU
|
0.042
|
Filter 6
|
Turbidity
|
NTU
|
0.052
|
Filter 7
|
Turbidity
|
NTU
|
0.050
|
Filter 8
|
Turbidity
|
NTU
|
0.047
|
Brantford POE
|
Turbidity
|
NTU
|
0.048
|
CCC Effluent
|
Log Removal
|
|
26.92
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.63
|
Brantford POE
|
Pressure
|
psi
|
97.14
|
SCADA Data - Monthly Averages
Distribution System |
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.22
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.08
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.59
|
Albion St. Booster
|
Pressure
|
psi
|
90.28
|
Tollgate Reservoir
|
Pressure
|
psi
|
59.01
|
Park Rd. Reservoir
|
Pressure
|
psi
|
78.70
|
Northwest Reservoir
|
Pressure
|
psi
|
85.50
|
Bell Lane
|
Pressure
|
psi
|
50.53
|
Fifth Ave
|
Pressure
|
psi
|
95.71
|
Lawren Harris
|
Pressure
|
psi
|
62.26
|
St. Andrews
|
Pressure
|
psi
|
91.01
|
Empey St.
|
Pressure
|
psi
|
82.36
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
September 2022 |
Treatment Operators Analysis
Source | Parameter | Units | MAC | AO/OG | Minimum | Maximum | Average |
Grand River
|
Ammonia
|
mg/L
|
|
|
0.03
|
0.13
|
0.08
|
Brantford POE
|
Ammonia
|
mg/L
|
|
|
0.26
|
0.52
|
0.39
|
Grand River
|
True Colour
|
PtCo
|
|
|
8
|
21
|
15
|
Brantford POE
|
True Colour
|
PtCo
|
|
5
|
0
|
1
|
0
|
Brantford POE
|
Aluminum
|
mg/L
|
|
0.100
|
0.053
|
0.190
|
0.138
|
Grand River
|
UV254
|
|
|
|
0.106
|
0.157
|
0.126
|
Brantford POE
|
UV254
|
|
|
|
0.028
|
0.044
|
0.036
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
|
0.16
|
0.81
|
0.69
|
Brantford POE
|
Free chlorine
|
mg/L
|
|
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
|
2.40
|
2.90
|
2.65
|
Brantford POE
|
Total Chlorine
|
mg/L
|
|
|
2.50
|
3.00
|
2.75
|
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
SCADA Data - Monthly Averages
Water Treatment Plant |
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
38.89
|
Brantford POE
|
Flow Rate
|
ML/d
|
34.32
|
Grand River
|
Turbidity
|
NTU
|
4.11
|
Filter 1
|
Turbidity
|
NTU
|
0.039
|
Filter 2
|
Turbidity
|
NTU
|
0.039
|
Filter 3
|
Turbidity
|
NTU
|
0.042
|
Filter 4
|
Turbidity
|
NTU
|
0.053
|
Filter 5
|
Turbidity
|
NTU
|
0.047
|
Filter 6
|
Turbidity
|
NTU
|
0.055
|
Filter 7
|
Turbidity
|
NTU
|
0.052
|
Filter 8
|
Turbidity
|
NTU
|
0.050
|
Brantford POE
|
Turbidity
|
NTU
|
0.057
|
CCC Effluent
|
Log Removal
|
|
20.93
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.62
|
Brantford POE
|
Pressure
|
psi
|
95.20
|
SCADA Data - Monthly Averages
Distribution System |
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.21
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.12
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.49
|
Albion St. Booster
|
Pressure
|
psi
|
90.47
|
Tollgate Reservoir
|
Pressure
|
psi
|
58.14
|
Park Rd. Reservoir
|
Pressure
|
psi
|
78.95
|
Northwest Reservoir
|
Pressure
|
psi
|
85.33
|
Bell Lane
|
Pressure
|
psi
|
48.80
|
Fifth Ave
|
Pressure
|
psi
|
94.13
|
Lawren Harris
|
Pressure
|
psi
|
64.39
|
St. Andrews
|
Pressure
|
psi
|
91.48
|
Empey St.
|
Pressure
|
psi
|
82.59
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
October 2022 |
Treatment Operators Analysis
Source | Parameter | Units | MAC | AO/OG | Minimum | Maximum | Average |
Grand River
|
Ammonia
|
mg/L
|
|
|
0.01
|
0.12
|
0.06
|
Brantford POE
|
Ammonia
|
mg/L
|
|
|
0.26
|
0.59
|
0.36
|
|
|
|
|
|
|
|
|
Grand River
|
True Colour
|
PtCo
|
|
|
8
|
18
|
14
|
Brantford POE
|
True Colour
|
PtCo
|
|
5
|
0
|
1
|
0
|
|
|
|
|
|
|
|
|
Brantford POE
|
Aluminum
|
mg/L
|
|
0.100
|
0.041
|
0.191
|
0.122
|
|
|
|
|
|
|
|
|
Grand River
|
UV254
|
|
|
|
0.104
|
0.123
|
0.110
|
Brantford POE
|
UV254
|
|
|
|
0.028
|
0.047
|
0.034
|
|
|
|
|
|
|
|
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
|
0.58
|
0.84
|
0.75
|
|
|
|
|
|
|
|
|
Brantford POE
|
Free chlorine
|
mg/L
|
|
|
0.1
|
0.1
|
0.1
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
|
2.40
|
2.90
|
2.61
|
Brantford POE
|
Total Chlorine
|
mg/L
|
|
|
2.50
|
3.00
|
2.71
|
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
SCADA Data - Monthly Averages
Water Treatment Plant |
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
38.53
|
Brantford POE
|
Flow Rate
|
ML/d
|
32.81
|
Grand River
|
Turbidity
|
NTU
|
3.09
|
Filter 1
|
Turbidity
|
NTU
|
0.041
|
Filter 2
|
Turbidity
|
NTU
|
0.038
|
Filter 3
|
Turbidity
|
NTU
|
0.039
|
Filter 4
|
Turbidity
|
NTU
|
0.046
|
Filter 5
|
Turbidity
|
NTU
|
0.042
|
Filter 6
|
Turbidity
|
NTU
|
0.053
|
Filter 7
|
Turbidity
|
NTU
|
0.048
|
Filter 8
|
Turbidity
|
NTU
|
0.048
|
Brantford POE
|
Turbidity
|
NTU
|
0.055
|
CCC Effluent
|
Log Removal
|
|
14.50
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.60
|
Brantford POE
|
Pressure
|
psi
|
96.81
|
SCADA Data - Monthly Averages
Distribution System |
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.20
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.26
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.57
|
Albion St. Booster
|
Pressure
|
psi
|
90.87
|
Tollgate Reservoir
|
Pressure
|
psi
|
58.03
|
Park Rd. Reservoir
|
Pressure
|
psi
|
79.36
|
Northwest Reservoir
|
Pressure
|
psi
|
84.92
|
Bell Lane
|
Pressure
|
psi
|
50.38
|
Fifth Ave
|
Pressure
|
psi
|
95.83
|
Lawren Harris
|
Pressure
|
psi
|
64.50
|
St. Andrews
|
Pressure
|
psi
|
92.13
|
Empey St.
|
Pressure
|
psi
|
82.57
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
November 2022 |
Treatment Operators Analysis
Source | Parameter | Units | MAC | AO/OG | Minimum | Maximum | Average |
Grand River
|
Ammonia
|
mg/L
|
|
|
0.01
|
0.13
|
0.06
|
Brantford POE
|
Ammonia
|
mg/L
|
|
|
0.21
|
0.51
|
0.33
|
|
|
|
|
|
|
|
|
Grand River
|
True Colour
|
PtCo
|
|
|
7
|
17
|
12
|
Brantford POE
|
True Colour
|
PtCo
|
|
5
|
0
|
2
|
0.54
|
|
|
|
|
|
|
|
|
Brantford POE
|
Aluminum
|
mg/L
|
|
0.100
|
0.017
|
0.151
|
0.096
|
|
|
|
|
|
|
|
|
Grand River
|
UV254
|
|
|
|
0.084
|
0.137
|
0.099
|
Brantford POE
|
UV254
|
|
|
|
0.032
|
0.055
|
0.042
|
|
|
|
|
|
|
|
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
|
0.50
|
0.87
|
0.65
|
|
|
|
|
|
|
|
|
Brantford POE
|
Free chlorine
|
mg/L
|
|
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
|
2.40
|
2.80
|
2.58
|
Brantford POE
|
Total Chlorine
|
mg/L
|
|
|
2.50
|
2.90
|
2.68
|
Definitions:
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
SCADA Data - Monthly Averages
Water Treatment Plant |
Source
|
Parameter
|
Units
|
Monthly Average
|
|
Grand River
|
Flow Rate
|
ML/d
|
37.83
|
|
Brantford POE
|
Flow Rate
|
ML/d
|
31.12
|
|
|
|
|
|
|
Grand River
|
Turbidity
|
NTU
|
2.77
|
|
Filter 1
|
Turbidity
|
NTU
|
0.037
|
|
Filter 2
|
Turbidity
|
NTU
|
0.034
|
|
Filter 3
|
Turbidity
|
NTU
|
0.036
|
|
Filter 4
|
Turbidity
|
NTU
|
0.044
|
|
Filter 5
|
Turbidity
|
NTU
|
0.039
|
|
Filter 6
|
Turbidity
|
NTU
|
0.049
|
|
Filter 7
|
Turbidity
|
NTU
|
0.046
|
|
Filter 8
|
Turbidity
|
NTU
|
0.045
|
|
Brantford POE
|
Turbidity
|
NTU
|
0.049
|
|
|
|
|
|
|
CCC Effluent
|
Log Removal
|
|
10.72
|
|
|
|
|
|
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.58
|
|
|
|
|
|
|
Brantford POE
|
Pressure
|
psi
|
96.97
|
|
SCADA Data - Monthly Averages
Distribution System |
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.35
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.30
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.50
|
|
|
|
|
Albion St. Booster
|
Pressure
|
psi
|
90.76
|
Tollgate Reservoir
|
Pressure
|
psi
|
58.20
|
Park Rd. Reservoir
|
Pressure
|
psi
|
78.88
|
Northwest Reservoir
|
Pressure
|
psi
|
85.03
|
Bell Lane
|
Pressure
|
psi
|
50.65
|
Fifth Ave
|
Pressure
|
psi
|
96.32
|
Lawren Harris
|
Pressure
|
psi
|
64.47
|
St. Andrews
|
Pressure
|
psi
|
93.24
|
Empey St.
|
Pressure
|
psi
|
82.65
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
December 2022 |
Treatment Operators Analysis - December 2022
Source | Parameter | Units | MAC | AO/OG | Minimum | Maximum | Average |
Grand River
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0
|
0.19
|
0.07
|
Brantford POE
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.18
|
0.46
|
0.31
|
Grand River
|
True Colour
|
PtCo
|
Not applicable
|
Not applicable
|
8
|
23
|
12.5
|
Brantford POE
|
True Colour
|
PtCo
|
Not applicable
|
5
|
0
|
2
|
1
|
Brantford POE
|
Aluminum
|
mg/L
|
Not applicable
|
0.100
|
0.021
|
0.072
|
0.051
|
Grand River
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.090
|
0.118
|
0.102
|
Brantford POE
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.036
|
0.069
|
0.048
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
Not applicable
|
0.51
|
0.78
|
0.67
|
Brantford POE
|
Free chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
Not applicable
|
2.30
|
2.80
|
2.57
|
Brantford POE
|
Total Chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
2.40
|
2.90
|
2.67
|
Definitions:
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
SCADA Data - Monthly Averages - December 2022
Water Treatment Plant |
Source
|
Parameter
|
Units
|
Monthly Average
|
|
|
Grand River
|
Flow Rate
|
ML/d
|
38.00
|
|
|
Brantford POE
|
Flow Rate
|
ML/d
|
30.50
|
|
|
Grand River
|
Turbidity
|
NTU
|
3.14
|
|
|
Filter 1
|
Turbidity
|
NTU
|
0.034
|
|
|
Filter 2
|
Turbidity
|
NTU
|
0.032
|
|
|
Filter 3
|
Turbidity
|
NTU
|
0.034
|
|
|
Filter 4
|
Turbidity
|
NTU
|
0.041
|
|
|
Filter 5
|
Turbidity
|
NTU
|
0.035
|
|
|
Filter 6
|
Turbidity
|
NTU
|
0.047
|
|
|
Filter 7
|
Turbidity
|
NTU
|
0.043
|
|
|
Filter 8
|
Turbidity
|
NTU
|
0.042
|
|
|
Brantford POE
|
Turbidity
|
NTU
|
0.047
|
|
|
CCC Effluent
|
Log Removal
|
Not applicable
|
8.73
|
|
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.58
|
|
|
Brantford POE
|
Pressure
|
psi
|
96.92
|
|
|
SCADA Data - Monthly Averages - December 2022
Distribution System |
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.40
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.38
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.52
|
Albion St. Booster
|
Pressure
|
psi
|
90.87
|
Tollgate Reservoir
|
Pressure
|
psi
|
57.31
|
Park Rd. Reservoir
|
Pressure
|
psi
|
79.02
|
Northwest Reservoir
|
Pressure
|
psi
|
85.41
|
Bell Lane
|
Pressure
|
psi
|
50.60
|
Fifth Ave
|
Pressure
|
psi
|
96.26
|
Lawren Harris
|
Pressure
|
psi
|
64.62
|
St. Andrews
|
Pressure
|
psi
|
93.52
|
Empey St.
|
Pressure
|
psi
|
82.84
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|