March 2021 |
SCADA Data - Monthly Averages
Water Treatment Plant
|
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
36.87
|
Brantford POE
|
Flow Rate
|
ML/d
|
30.67
|
Grand River
|
Turbidity
|
NTU
|
9.69
|
Filter 1
|
Turbidity
|
NTU
|
0.032
|
Filter 2
|
Turbidity
|
NTU
|
0.032
|
Filter 3
|
Turbidity
|
NTU
|
0.032
|
Filter 4
|
Turbidity
|
NTU
|
0.032
|
Filter 5
|
Turbidity
|
NTU
|
0.033
|
Filter 6
|
Turbidity
|
NTU
|
0.040
|
Filter 7
|
Turbidity
|
NTU
|
0.039
|
Filter 8
|
Turbidity
|
NTU
|
0.034
|
Brantford POE
|
Turbidity
|
NTU
|
0.043
|
CCC Effluent
|
Log Removal
|
Not applicable
|
9.48
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.59
|
Brantford POE
|
Pressure
|
psi
|
97.05
|
Distribution System
|
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.51
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.54
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.52
|
Albion St. Booster
|
Pressure
|
psi
|
90.85
|
Tollgate Reservoir
|
Pressure
|
psi
|
59.63
|
Park Rd. Reservoir
|
Pressure
|
psi
|
79.30
|
Northwest Reservoir
|
Pressure
|
psi
|
85.98
|
Bell Lane
|
Pressure
|
psi
|
50.74
|
Fifth Ave
|
Pressure
|
psi
|
102.76
|
Lawren Harris
|
Pressure
|
psi
|
65.10
|
St. Andrews
|
Pressure
|
psi
|
93.44
|
Empey St.
|
Pressure
|
psi
|
82.68
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
Treatment Operators Analysis
Source
|
Parameter
|
Units
|
MAC
|
AO/OG
|
Minimum
|
Maximum
|
Average
|
Grand River
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.00
|
0.23
|
0.10
|
Brantford POE
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.22
|
0.49
|
0.35
|
Grand River
|
True Colour
|
PtCo
|
Not applicable
|
Not applicable
|
11.0
|
28.0
|
17.0
|
Brantford POE
|
True Colour
|
PtCo
|
Not applicable
|
5
|
0.0
|
2.0
|
0.5
|
Brantford POE
|
Aluminum
|
mg/L
|
Not applicable
|
0.100
|
0.003
|
0.105
|
0.052
|
Grand River
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.112
|
0.202
|
0.144
|
Brantford POE
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.033
|
0.057
|
0.045
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
Not applicable
|
0.530
|
0.790
|
0.650
|
Brantford POE
|
Free chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
Not applicable
|
2.40
|
3.00
|
2.60
|
Brantford POE
|
Total Chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
2.50
|
3.10
|
2.70
|
Definitions:
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
April 2021 |
SCADA Data - Monthly Averages
Water Treatment Plant
|
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
36.87
|
Brantford POE
|
Flow Rate
|
ML/d
|
29.25
|
Grand River
|
Turbidity
|
NTU
|
9.50
|
Filter 1
|
Turbidity
|
NTU
|
0.040
|
Filter 2
|
Turbidity
|
NTU
|
0.039
|
Filter 3
|
Turbidity
|
NTU
|
0.038
|
Filter 4
|
Turbidity
|
NTU
|
0.041
|
Filter 5
|
Turbidity
|
NTU
|
0.042
|
Filter 6
|
Turbidity
|
NTU
|
0.049
|
Filter 7
|
Turbidity
|
NTU
|
0.047
|
Filter 8
|
Turbidity
|
NTU
|
0.042
|
Brantford POE
|
Turbidity
|
NTU
|
0.060
|
CCC Effluent
|
Log Removal
|
Not applicable
|
12.37
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.59
|
Brantford POE
|
Pressure
|
psi
|
97.01
|
Distribution System
|
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.30
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.31
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.47
|
Albion St. Booster
|
Pressure
|
psi
|
91.00
|
Tollgate Reservoir
|
Pressure
|
psi
|
59.47
|
Park Rd. Reservoir
|
Pressure
|
psi
|
79.40
|
Northwest Reservoir
|
Pressure
|
psi
|
86.08
|
Bell Lane
|
Pressure
|
psi
|
50.72
|
Fifth Ave
|
Pressure
|
psi
|
Offline
|
Lawren Harris
|
Pressure
|
psi
|
65.24
|
St. Andrews
|
Pressure
|
psi
|
93.04
|
Empey St.
|
Pressure
|
psi
|
82.96
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
Treatment Operators Analysis
Source
|
Parameter
|
Units
|
MAC
|
AO/OG
|
Minimum
|
Maximum
|
Average
|
Grand River
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.00
|
0.19
|
0.09
|
Brantford POE
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.19
|
0.60
|
0.34
|
Grand River
|
True Colour
|
PtCo
|
Not applicable
|
Not applicable
|
11.0
|
30.0
|
20.0
|
Brantford POE
|
True Colour
|
PtCo
|
Not applicable
|
5
|
0.0
|
2.0
|
0.0
|
Brantford POE
|
Aluminum
|
mg/L
|
Not applicable
|
0.100
|
0.029
|
0.186
|
0.076
|
Grand River
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.130
|
0.217
|
0.156
|
Brantford POE
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.035
|
0.057
|
0.042
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
Not applicable
|
0.540
|
0.840
|
0.690
|
Brantford POE
|
Free chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
Not applicable
|
2.40
|
2.80
|
2.59
|
Brantford POE
|
Total Chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
2.50
|
2.90
|
2.69
|
Definitions:
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
May 2021 |
SCADA Data - Monthly Averages
Water Treatment Plant
|
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
40.10
|
Brantford POE
|
Flow Rate
|
ML/d
|
34.18
|
Grand River
|
Turbidity
|
NTU
|
8.43
|
Filter 1
|
Turbidity
|
NTU
|
0.046
|
Filter 2
|
Turbidity
|
NTU
|
0.044
|
Filter 3
|
Turbidity
|
NTU
|
0.046
|
Filter 4
|
Turbidity
|
NTU
|
0.049
|
Filter 5
|
Turbidity
|
NTU
|
0.048
|
Filter 6
|
Turbidity
|
NTU
|
0.057
|
Filter 7
|
Turbidity
|
NTU
|
0.054
|
Filter 8
|
Turbidity
|
NTU
|
0.051
|
Brantford POE
|
Turbidity
|
NTU
|
0.078
|
CCC Effluent
|
Log Removal
|
Not applicable
|
16.29
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.62
|
Brantford POE
|
Pressure
|
psi
|
97.24
|
Distribution System
|
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.26
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.18
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.46
|
Albion St. Booster
|
Pressure
|
psi
|
90.56
|
Tollgate Reservoir
|
Pressure
|
psi
|
60.00
|
Park Rd. Reservoir
|
Pressure
|
psi
|
79.10
|
Northwest Reservoir
|
Pressure
|
psi
|
85.29
|
Bell Lane
|
Pressure
|
psi
|
50.77
|
Fifth Ave
|
Pressure
|
psi
|
O.O.S.
|
Lawren Harris
|
Pressure
|
psi
|
65.12
|
St. Andrews
|
Pressure
|
psi
|
92.03
|
Empey St.
|
Pressure
|
psi
|
82.61
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S. - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
Treatment Operators Analysis
Source
|
Parameter
|
Units
|
MAC
|
AO/OG
|
Minimum
|
Maximum
|
Average
|
Grand River
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.01
|
0.15
|
0.08
|
Brantford POE
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.21
|
0.56
|
0.34
|
Grand River
|
True Colour
|
PtCo
|
Not applicable
|
Not applicable
|
12.0
|
20.0
|
16.5
|
Brantford POE
|
True Colour
|
PtCo
|
Not applicable
|
5
|
0.0
|
2.0
|
0.0
|
Brantford POE
|
Aluminum
|
mg/L
|
Not applicable
|
0.100
|
0.020
|
0.165
|
0.099
|
Grand River
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.123
|
0.154
|
0.135
|
Brantford POE
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.030
|
0.047
|
0.035
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
Not applicable
|
0.540
|
0.810
|
0.650
|
Brantford POE
|
Free chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
Not applicable
|
2.40
|
3.00
|
2.63
|
Brantford POE
|
Total Chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
2.50
|
3.10
|
2.73
|
Definitions:
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
June 2021 |
SCADA Data - Monthly Averages
Water Treatment Plant
|
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
41.49
|
Brantford POE
|
Flow Rate
|
ML/d
|
37.34
|
Grand River
|
Turbidity
|
NTU
|
8.16
|
Filter 1
|
Turbidity
|
NTU
|
0.040
|
Filter 2
|
Turbidity
|
NTU
|
0.039
|
Filter 3
|
Turbidity
|
NTU
|
0.041
|
Filter 4
|
Turbidity
|
NTU
|
0.046
|
Filter 5
|
Turbidity
|
NTU
|
0.043
|
Filter 6
|
Turbidity
|
NTU
|
0.050
|
Filter 7
|
Turbidity
|
NTU
|
0.050
|
Filter 8
|
Turbidity
|
NTU
|
0.048
|
Brantford POE
|
Turbidity
|
NTU
|
0.061
|
CCC Effluent
|
Log Removal
|
Not applicable
|
25.59
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.65
|
Brantford POE
|
Pressure
|
psi
|
97.22
|
Distribution System
|
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.01
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
1.86
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.40
|
Albion St. Booster
|
Pressure
|
psi
|
90.60
|
Tollgate Reservoir
|
Pressure
|
psi
|
59.44
|
Park Rd. Reservoir
|
Pressure
|
psi
|
78.93
|
Northwest Reservoir
|
Pressure
|
psi
|
84.34
|
Bell Lane
|
Pressure
|
psi
|
50.67
|
Fifth Ave
|
Pressure
|
psi
|
O.O.S.
|
Lawren Harris
|
Pressure
|
psi
|
64.61
|
St. Andrews
|
Pressure
|
psi
|
91.34
|
Empey St.
|
Pressure
|
psi
|
82.38
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S. - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
Treatment Operators Analysis
Source
|
Parameter
|
Units
|
MAC
|
AO/OG
|
Minimum
|
Maximum
|
Average
|
Grand River
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.05
|
0.22
|
0.13
|
Brantford POE
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.21
|
0.45
|
0.35
|
Grand River
|
True Colour
|
PtCo
|
Not applicable
|
Not applicable
|
13
|
25
|
18.6
|
Brantford POE
|
True Colour
|
PtCo
|
Not applicable
|
5
|
0.0
|
2.0
|
0.3
|
Brantford POE
|
Aluminum
|
mg/L
|
Not applicable
|
0.100
|
0.039
|
0.142
|
0.075
|
Grand River
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.131
|
0.160
|
0.144
|
Brantford POE
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.032
|
0.048
|
0.038
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
Not applicable
|
0.33
|
0.740
|
0.640
|
Brantford POE
|
Free chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
Not applicable
|
2.50
|
2.90
|
2.68
|
Brantford POE
|
Total Chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
2.60
|
3.00
|
2.78
|
Definitions:
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
July 2021 |
SCADA Data - Monthly Averages
Water Treatment Plant
|
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
38.00
|
Brantford POE
|
Flow Rate
|
ML/d
|
34.84
|
Grand River
|
Turbidity
|
NTU
|
6.74
|
Filter 1
|
Turbidity
|
NTU
|
0.047
|
Filter 2
|
Turbidity
|
NTU
|
0.044
|
Filter 3
|
Turbidity
|
NTU
|
0.048
|
Filter 4
|
Turbidity
|
NTU
|
0.052
|
Filter 5
|
Turbidity
|
NTU
|
0.049
|
Filter 6
|
Turbidity
|
NTU
|
0.055
|
Filter 7
|
Turbidity
|
NTU
|
0.054
|
Filter 8
|
Turbidity
|
NTU
|
0.051
|
Brantford POE
|
Turbidity
|
NTU
|
0.059
|
CCC Effluent
|
Log Removal
|
Not applicable
|
28.41
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.66
|
Brantford POE
|
Pressure
|
psi
|
96.88
|
Distribution System
|
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
1.85
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
1.85
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.29
|
Albion St. Booster
|
Pressure
|
psi
|
90.70
|
Tollgate Reservoir
|
Pressure
|
psi
|
59.10
|
Park Rd. Reservoir
|
Pressure
|
psi
|
78.98
|
Northwest Reservoir
|
Pressure
|
psi
|
84.35
|
Bell Lane
|
Pressure
|
psi
|
50.39
|
Fifth Ave
|
Pressure
|
psi
|
O.O.S.
|
Lawren Harris
|
Pressure
|
psi
|
64.58
|
St. Andrews
|
Pressure
|
psi
|
91.48
|
Empey St.
|
Pressure
|
psi
|
82.46
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S. - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
Treatment Operators Analysis
Source
|
Parameter
|
Units
|
MAC
|
AO/OG
|
Minimum
|
Maximum
|
Average
|
Grand River
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.04
|
0.30
|
0.12
|
Brantford POE
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.23
|
0.49
|
0.36
|
Grand River
|
True Colour
|
PtCo
|
Not applicable
|
Not applicable
|
53.0
|
118.0
|
81.6
|
Brantford POE
|
True Colour
|
PtCo
|
Not applicable
|
5
|
0.0
|
3.0
|
0.3
|
Brantford POE
|
Aluminum
|
mg/L
|
Not applicable
|
0.100
|
0.047
|
0.150
|
0.102
|
Grand River
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.133
|
0.170
|
0.147
|
Brantford POE
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.033
|
0.042
|
0.036
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
Not applicable
|
0.53
|
0.780
|
0.650
|
Brantford POE
|
Free chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
Not applicable
|
2.50
|
2.90
|
2.71
|
Brantford POE
|
Total Chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
2.60
|
3.00
|
2.81
|
Definitions:
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
August 2021 |
SCADA Data - Monthly Averages
Water Treatment Plant
|
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
39.62
|
Brantford POE
|
Flow Rate
|
ML/d
|
36.33
|
Grand River
|
Turbidity
|
NTU
|
6.17
|
Filter 1
|
Turbidity
|
NTU
|
0.053
|
Filter 2
|
Turbidity
|
NTU
|
0.046
|
Filter 3
|
Turbidity
|
NTU
|
0.051
|
Filter 4
|
Turbidity
|
NTU
|
0.052
|
Filter 5
|
Turbidity
|
NTU
|
0.050
|
Filter 6
|
Turbidity
|
NTU
|
0.059
|
Filter 7
|
Turbidity
|
NTU
|
0.056
|
Filter 8
|
Turbidity
|
NTU
|
0.055
|
Brantford POE
|
Turbidity
|
NTU
|
0.060
|
CCC Effluent
|
Log Removal
|
Not applicable
|
28.25
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.68
|
Brantford POE
|
Pressure
|
psi
|
96.94
|
Distribution System
|
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
1.94
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
1.78
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.23
|
Albion St. Booster
|
Pressure
|
psi
|
90.44
|
Tollgate Reservoir
|
Pressure
|
psi
|
59.29
|
Park Rd. Reservoir
|
Pressure
|
psi
|
78.63
|
Northwest Reservoir
|
Pressure
|
psi
|
85.62
|
Bell Lane
|
Pressure
|
psi
|
50.40
|
Fifth Ave
|
Pressure
|
psi
|
O.O.S.
|
Lawren Harris
|
Pressure
|
psi
|
64.50
|
St. Andrews
|
Pressure
|
psi
|
91.14
|
Empey St.
|
Pressure
|
psi
|
82.03
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S. - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
Treatment Operators Analysis
Source
|
Parameter
|
Units
|
MAC
|
AO/OG
|
Minimum
|
Maximum
|
Average
|
Grand River
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.03
|
0.25
|
0.10
|
Brantford POE
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.24
|
0.46
|
0.36
|
Grand River
|
True Colour
|
PtCo
|
Not applicable
|
Not applicable
|
10.0
|
22.0
|
16.6
|
Brantford POE
|
True Colour
|
PtCo
|
Not applicable
|
5
|
0.0
|
1.0
|
0.0
|
Brantford POE
|
Aluminum
|
mg/L
|
Not applicable
|
0.100
|
0.066
|
0.146
|
0.115
|
Grand River
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.136
|
0.156
|
0.142
|
Brantford POE
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.030
|
0.042
|
0.036
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
Not applicable
|
0.640
|
0.750
|
0.700
|
Brantford POE
|
Free chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
Not applicable
|
2.50
|
2.90
|
2.70
|
Brantford POE
|
Total Chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
2.60
|
3.00
|
2.80
|
Definitions:
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
September 2021 |
SCADA Data - Monthly Averages
Water Treatment Plant
|
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
36.54
|
Brantford POE
|
Flow Rate
|
ML/d
|
33.32
|
Grand River
|
Turbidity
|
NTU
|
8.99
|
Filter 1
|
Turbidity
|
NTU
|
0.048
|
Filter 2
|
Turbidity
|
NTU
|
0.044
|
Filter 3
|
Turbidity
|
NTU
|
0.047
|
Filter 4
|
Turbidity
|
NTU
|
0.050
|
Filter 5
|
Turbidity
|
NTU
|
0.048
|
Filter 6
|
Turbidity
|
NTU
|
0.059
|
Filter 7
|
Turbidity
|
NTU
|
0.053
|
Filter 8
|
Turbidity
|
NTU
|
0.051
|
Brantford POE
|
Turbidity
|
NTU
|
0.054
|
CCC Effluent
|
Log Removal
|
Not applicable
|
22.30
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.65
|
Brantford POE
|
Pressure
|
psi
|
96.93
|
Distribution System
|
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.10
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
1.97
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.30
|
Albion St. Booster
|
Pressure
|
psi
|
90.77
|
Tollgate Reservoir
|
Pressure
|
psi
|
58.49
|
Park Rd. Reservoir
|
Pressure
|
psi
|
79.06
|
Northwest Reservoir
|
Pressure
|
psi
|
85.67
|
Bell Lane
|
Pressure
|
psi
|
50.60
|
Fifth Ave
|
Pressure
|
psi
|
O.O.S.
|
Lawren Harris
|
Pressure
|
psi
|
64.47
|
St. Andrews
|
Pressure
|
psi
|
75.19
|
Empey St.
|
Pressure
|
psi
|
82.57
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S. - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
Treatment Operators Analysis
Source
|
Parameter
|
Units
|
MAC
|
AO/OG
|
Minimum
|
Maximum
|
Average
|
Grand River
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.06
|
0.34
|
0.13
|
Brantford POE
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.25
|
0.53
|
0.35
|
Grand River
|
True Colour
|
PtCo
|
Not applicable
|
Not applicable
|
14.0
|
43.0
|
22.0
|
Brantford POE
|
True Colour
|
PtCo
|
Not applicable
|
5
|
0.0
|
2.0
|
0.0
|
Brantford POE
|
Aluminum
|
mg/L
|
Not applicable
|
0.100
|
0.021
|
0.094
|
0.057
|
Grand River
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.132
|
0.269
|
0.170
|
Brantford POE
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.027
|
0.060
|
0.039
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
Not applicable
|
0.590
|
0.810
|
0.660
|
Brantford POE
|
Free chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
Not applicable
|
2.50
|
2.80
|
2.67
|
Brantford POE
|
Total Chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
2.60
|
2.90
|
2.77
|
Definitions:
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
October 2021 |
SCADA Data - Monthly Averages
Water Treatment Plant
|
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
39.09
|
Brantford POE
|
Flow Rate
|
ML/d
|
33.31
|
Grand River
|
Turbidity
|
NTU
|
7.48
|
Filter 1
|
Turbidity
|
NTU
|
0.042
|
Filter 2
|
Turbidity
|
NTU
|
0.040
|
Filter 3
|
Turbidity
|
NTU
|
0.042
|
Filter 4
|
Turbidity
|
NTU
|
0.048
|
Filter 5
|
Turbidity
|
NTU
|
0.045
|
Filter 6
|
Turbidity
|
NTU
|
0.052
|
Filter 7
|
Turbidity
|
NTU
|
0.051
|
Filter 8
|
Turbidity
|
NTU
|
0.048
|
Brantford POE
|
Turbidity
|
NTU
|
0.044
|
CCC Effluent
|
Log Removal
|
Not applicable
|
16.29
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.63
|
Brantford POE
|
Pressure
|
psi
|
96.77
|
Distribution System
|
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.30
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.11
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.42
|
Albion St. Booster
|
Pressure
|
psi
|
89.80
|
Tollgate Reservoir
|
Pressure
|
psi
|
60.43
|
Park Rd. Reservoir
|
Pressure
|
psi
|
76.69
|
Northwest Reservoir
|
Pressure
|
psi
|
85.24
|
Bell Lane
|
Pressure
|
psi
|
50.52
|
Fifth Ave
|
Pressure
|
psi
|
96.02
|
Lawren Harris
|
Pressure
|
psi
|
65.01
|
St. Andrews
|
Pressure
|
psi
|
92.34
|
Empey St.
|
Pressure
|
psi
|
80.24
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S. - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
Treatment Operators Analysis
Source
|
Parameter
|
Units
|
MAC
|
AO/OG
|
Minimum
|
Maximum
|
Average
|
Grand River
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.06
|
0.18
|
0.11
|
Brantford POE
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.20
|
0.42
|
0.31
|
Grand River
|
True Colour
|
PtCo
|
Not applicable
|
Not applicable
|
20.0
|
36.0
|
26.0
|
Brantford POE
|
True Colour
|
PtCo
|
Not applicable
|
5
|
0.0
|
2.0
|
0.0
|
Brantford POE
|
Aluminum
|
mg/L
|
Not applicable
|
0.100
|
0.020
|
0.117
|
0.065
|
Grand River
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.183
|
0.250
|
0.201
|
Brantford POE
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.038
|
0.059
|
0.050
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
Not applicable
|
0.140
|
0.820
|
0.700
|
Brantford POE
|
Free chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
Not applicable
|
2.50
|
2.90
|
2.66
|
Brantford POE
|
Total Chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
2.60
|
3.00
|
2.76
|
Definitions:
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
November 2021 |
SCADA Data - Monthly Averages
Water Treatment Plant
|
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
36.96
|
Brantford POE
|
Flow Rate
|
ML/d
|
29.77
|
Grand River
|
Turbidity
|
NTU
|
4.20
|
Filter 1
|
Turbidity
|
NTU
|
0.033
|
Filter 2
|
Turbidity
|
NTU
|
0.031
|
Filter 3
|
Turbidity
|
NTU
|
0.032
|
Filter 4
|
Turbidity
|
NTU
|
0.038
|
Filter 5
|
Turbidity
|
NTU
|
0.032
|
Filter 6
|
Turbidity
|
NTU
|
0.041
|
Filter 7
|
Turbidity
|
NTU
|
0.037
|
Filter 8
|
Turbidity
|
NTU
|
0.041
|
Brantford POE
|
Turbidity
|
NTU
|
0.034
|
CCC Effluent
|
Log Removal
|
Not applicable
|
10.07
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.64
|
Brantford POE
|
Pressure
|
psi
|
96.79
|
Distribution System
|
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.50
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.47
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.65
|
Albion St. Booster
|
Pressure
|
psi
|
90.96
|
Tollgate Reservoir
|
Pressure
|
psi
|
58.37
|
Park Rd. Reservoir
|
Pressure
|
psi
|
79.09
|
Northwest Reservoir
|
Pressure
|
psi
|
85.70
|
Bell Lane
|
Pressure
|
psi
|
50.59
|
Fifth Ave
|
Pressure
|
psi
|
96.17
|
Lawren Harris
|
Pressure
|
psi
|
64.63
|
St. Andrews
|
Pressure
|
psi
|
92.82
|
Empey St.
|
Pressure
|
psi
|
82.79
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S. - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
Treatment Operators Analysis
Source
|
Parameter
|
Units
|
MAC
|
AO/OG
|
Minimum
|
Maximum
|
Average
|
Grand River
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.04
|
0.12
|
0.08
|
Brantford POE
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.22
|
0.57
|
0.35
|
Grand River
|
True Colour
|
PtCo
|
Not applicable
|
Not applicable
|
14.0
|
28.0
|
22.0
|
Brantford POE
|
True Colour
|
PtCo
|
Not applicable
|
5
|
0.0
|
3.0
|
0.0
|
Brantford POE
|
Aluminum
|
mg/L
|
Not applicable
|
0.100
|
0.021
|
0.137
|
0.070
|
Grand River
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.161
|
0.221
|
0.183
|
Brantford POE
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.042
|
0.069
|
0.056
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
Not applicable
|
0.540
|
0.790
|
0.680
|
Brantford POE
|
Free chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
Not applicable
|
2.60
|
2.80
|
2.64
|
Brantford POE
|
Total Chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
2.50
|
2.90
|
2.75
|
Definitions:
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|
December 2021 |
SCADA Data - Monthly Averages
Water Treatment Plant
|
Source
|
Parameter
|
Units
|
Monthly Average
|
Grand River
|
Flow Rate
|
ML/d
|
37.91
|
Brantford POE
|
Flow Rate
|
ML/d
|
30.11
|
Grand River
|
Turbidity
|
NTU
|
7.74
|
Filter 1
|
Turbidity
|
NTU
|
0.027
|
Filter 2
|
Turbidity
|
NTU
|
0.025
|
Filter 3
|
Turbidity
|
NTU
|
0.027
|
Filter 4
|
Turbidity
|
NTU
|
0.031
|
Filter 5
|
Turbidity
|
NTU
|
0.027
|
Filter 6
|
Turbidity
|
NTU
|
0.036
|
Filter 7
|
Turbidity
|
NTU
|
0.033
|
Filter 8
|
Turbidity
|
NTU
|
0.034
|
Brantford POE
|
Turbidity
|
NTU
|
0.031
|
CCC Effluent
|
Log Removal
|
Not applicable
|
8.24
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
2.56
|
Brantford POE
|
Pressure
|
psi
|
96.76
|
Distribution System
|
Source
|
Parameter
|
Units
|
Monthly Average
|
Tollgate Reservoir
|
Total Chlorine
|
mg/L
|
2.47
|
Park Rd. Reservoir
|
Total Chlorine
|
mg/L
|
2.52
|
Northwest Reservoir
|
Total Chlorine
|
mg/L
|
2.65
|
Albion St. Booster
|
Pressure
|
psi
|
90.94
|
Tollgate Reservoir
|
Pressure
|
psi
|
58.83
|
Park Rd. Reservoir
|
Pressure
|
psi
|
78.71
|
Northwest Reservoir
|
Pressure
|
psi
|
85.45
|
Bell Lane
|
Pressure
|
psi
|
50.50
|
Fifth Ave
|
Pressure
|
psi
|
96.10
|
Lawren Harris
|
Pressure
|
psi
|
64.93
|
St. Andrews
|
Pressure
|
psi
|
93.03
|
Empey St.
|
Pressure
|
psi
|
82.43
|
Definitions:
SCADA - Supervisory Control and Data Acquisition
O.O.S. - Out of Service
CCC - Chlorine Contact Chambers
Log Removal – a shorthand term for log10 removal, used in reference to the physical-chemical treatment of water to remove, kill, or inactivate pathogenic organisms.
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
Treatment Operators Analysis
Source
|
Parameter
|
Units
|
MAC
|
AO/OG
|
Minimum
|
Maximum
|
Average
|
Grand River
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.03
|
0.28
|
0.09
|
Brantford POE
|
Ammonia
|
mg/L
|
Not applicable
|
Not applicable
|
0.20
|
0.45
|
0.32
|
Grand River
|
True Colour
|
PtCo
|
Not applicable
|
Not applicable
|
15.0
|
29.0
|
21.0
|
Brantford POE
|
True Colour
|
PtCo
|
Not applicable
|
5
|
0.0
|
2.0
|
0.0
|
Brantford POE
|
Aluminum
|
mg/L
|
Not applicable
|
0.100
|
0.012
|
0.088
|
0.042
|
Grand River
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.145
|
0.199
|
0.169
|
Brantford POE
|
UV254
|
Not applicable
|
Not applicable
|
Not applicable
|
0.046
|
0.065
|
0.054
|
Brantford POE
|
Fluoride
|
mg/L
|
1.50
|
Not applicable
|
0.540
|
0.820
|
0.690
|
Brantford POE
|
Free chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
0.10
|
0.10
|
0.10
|
Brantford POE
|
Combined Chlorine
|
mg/L
|
3.00
|
Not applicable
|
2.43
|
2.90
|
2.59
|
Brantford POE
|
Total Chlorine
|
mg/L
|
Not applicable
|
Not applicable
|
2.53
|
3.00
|
2.69
|
Definitions:
MAC - Maximum Acceptable Concentration
AO/OG - Aesthetic Objective/Operational Guideline
Combined Chlorine - The concentration of residual chlorine that is combined with ammonia (NH3), organic nitrogen, or both in water as chloramine, yet is still available to oxidize organic matter and act as a disinfectant. Combined chlorine can be accurately estimated as the difference between the measured total chlorine and measure or known free chlorine residual.
|